VeriSafe™ AVT Instruction Manual Revision Notice

Instruction Manual Revision: 15

 

VeriSafe™ AVT Models: VS-AVT-C08-L10, VS-AVT-C02-L03, VS-AVT-C02-L03U and VS-AVT-C08-L10U

Instruction Manual Revision: 0

Date: 7/2/2024

Author: Alan Bond

Description of Instruction Manual Change

 

What is a Filtered Battery Indicator Module? (Panduit PN: VS-AVT-3IB-F)

A “filtered” Battery Indicator Module is the same Battery Indicator Module, yet it has an

additional component in line with each of the 3 red presence of voltage LED circuits. This is to

control high frequency electrical noise as, in some installations, this noise can be coupled from

powered feeders to an adjacent unpowered circuit in the same conduit. In these cases, the

energized conductors can generate a small high frequency induced voltage which may cause

the red LEDs for the AVT monitoring the unpowered adjacent circuit to be lit dimly, flicker, or in

some rare cases, illuminate when hazardous voltage is not actually present. 

 

We Recommend a Filtered Indicator:

  • If conductors of the circuit that the VeriSafe unit is installed on will be run along other circuits in the same conduit for some distance
  • If the circuits are powering noise sources such as drives or controllers that could induce that noise onto adjacent conductors
  • This is the best option for most circuits

 

Note: The presence of voltage circuits (the red LEDs) are not part of the safety function of the

VeriSafe AVT and only receiving a green LED is functionally safety rated (SIL3) and the green

light alone should be utilized for determining if the source conductor is deenergized.

Note: The green LED safety circuit is NOT impacted by these noise conditions. If hazardous

voltage is present, even in the presence of this electrical noise, VeriSafe will NOT issue a Green

light.

Product History of VS-AVT-C02-L03 and VS-AVT-C08-L10:

  • 5/25/2017-8/19/2019: Unfiltered
  • 8/19/2019-1/24/2022: Filtered
  • 1/24/2022-6/30/2024: Unfiltered
  • 7/1/2024 – Present: Filtered

 

QC#s with Filtered Indicators

VS-AVT-C08-L10 VS-AVT-C02-L03

847669101
847669102
847669103
847669104
>847669XXX

>847669062

 

 

For any questions or concerns, please reach out to Panduit Technical Support:

Email:    techsupport@panduit.com